140 Current Outputs Page
Section 5: Startup and meter configuration Reference, Installation, and Operations Manual
August 2014 3-9000-743 Rev U
5.6.8 Current Outputs Page
Figure 5-11 Field Setup Wizard - Meter Current Outputs Page
1. From the
Current Outputs Page, choose the desired settings:
Content:
Current output 1
Current output 2
Options: Actual flow rate (Uncorrected), Standard flow rate (Corrected),
Average flow velocity, Average sound velocity, Energy rate, or Mass rate
(Energy rate or Mass rate available if selected on Frequency outputs page)
Direction:
Reverse
Forward
Absolute
Full scale volumetric flow rate used with output:
Options: US Customary - ft
3
/sec.,hr, day or Metric - m
3
/sec.,hr, day
Alarm Action:
High - 20 mA
Low - 4 mA
Hold Last Value
Very Low - 3.5 mA
Very High - 20.5 mA
None