Operation
6.8 PROFINET IO
Drive converter cabinet units
246 Operating Instructions, 10/2008, A5E00288214A
Settings in STARTER
The following settings are required in STARTER for communication via PROFINET:
Extras -> Set PG/PC interface
Figure 6-36 Set the PG/PC interface
Assignment of the IP address and the name for the PROFINET interface of the drive unit
Use the STARTER to assign an IP address and a name to the PROFINET interface (e.g.
CBE20).
Requirement:
Connect the direct Ethernet cable from the PG/PC to the PROFINET interface of the
CU320 Control Unit.
Switch on Control Unit CU320
The accessible nodes must be searched in the STARTER:
Project -> Accessible nodes
Subsequently the nodes found are displayed in the interactive screen.