Operation
6.8 PROFINET IO
Drive converter cabinet units
244 Operating Instructions, 10/2008, A5E00288214A
6.8 PROFINET IO
6.8.1 Activating online operation: STARTER via PROFINET IO
Description
The following options are available for online operation via PROFINET IO:
Online operation via IP
Prerequisites
STARTER with version ≥ 4.1.1
Firmware version ≥ 2.5.1
CBE20
STARTER via PROFINET IO (example)
(WKHUQHW
DGDSWHU
352),1(7
LQWHUIDFH
3*3&67$57(5
&8
'HYLFH
,3
352),1(7
Figure 6-34 STARTER via PROFINET (example)
Procedure, establishing online operation with PROFINET
1. Set the IP address in Windows XP
The PC/PG is referred here to a fixed, free IP address.
2. Settings in STARTER
3. Assignment of the IP address and the name for the PROFINET interface of the drive unit
The PROFINET interface must be "baptized" so that the STARTER can establish
communication.
4. Select online operation in STARTER.